Solis-80K-5G, Solis-100K-HV-5G

Reliability Safety Capacity

Solis-80K-5G, Solis-100K-HV-5G

 

Leading Features

 

  • Max. 13A per string, 150% DC overloading capability
  • Efficient logic algorithm, over 99% max. Efficiency
  • Remote & local intelligent IV scan function
  • Volt-watt work mode integrated
  • Optional anti-PID function integrated
  • 10 individual MPPT, lower dismatch loss
  • String monitoring, shorter O&M time
  • Leakage current repression technology
  • DC input reverse alarm
  • Reactive power compensation function

Description

Fan cooling
Cooling concept
Ten
MPPT
WiFi/GPRS
Real time monitoring
180-1000V
MPPT voltage range
IP65
Ingress protection
App Store

IOS/Android

Technical specifications

Input DC

  • Recommended Max. DC input power (kW):
    112
  • Max. DC input voltage(V):
    1100
  • Nominal DC voltage(V):
    600
  • Start-up voltage(V):
    200
  • MPPT voltage range(V):
    180-1000
  • Full load MPPT voltage range (V):
    505-850
  • Max. input current (A):
    26A
  • Max. Short Circuit current for each MPPT:
    40A
  • MPPT number/Max input strings number:
    8/A:2; B:2; C:2; D:2; E:2; F:2; G:2; H:2

Output AC

  • Rated output power(kW):
    80kW
  • Max. apparent output power(kVA):
    88kVA
  • Max. output power:
    88kW
  • Rated grid voltage(V):
    3/N/PE, 230/400V
  • Rated grid frequency(Hz):
    50Hz/60Hz
  • AC Output frequency range:
    45 ~ 55Hz/55 ~ 60Hz
  • Rated grid current:
    115.5A
  • Max. output current:
    133.7A
  • Power Factor (at rated output power):
    0.8leading ... 0.8lagging
  • THDi (at rated output power):
    <3%
  • DC injection current:
    0.5%In

Efficiency

  • Max.efficiency:
    99.00%
  • EU efficiency:
    98.40%
  • MPPT efficiency:
    99.5%

Protection

  • Anti-islanding protection:
    Yes
  • DC reverse-polarity protection:
    Yes
  • Insulation resistance monitoring:
    Yes
  • Residual current detection:
    Yes
  • DC Surge protection:
    Type Ⅱ /Type Ⅰ + Ⅱ
  • AC Surge protection:
    Type Ⅱ
  • Grid monitoring:
    Yes
  • Strings Monitoring:
    Yes
  • I/V Curve scanning:
    Yes
  • Anti-PID function:
    Yes
  • DC are-fault circuit protection:
    Yes
  • Intergarated DC switch:
    Yes
  • Intergarated AC switch:
    Optional

General Data

  • Dimensins(W*H*D):
    1050W*567H*286.5D
  • Weight(kg):
    <85kg
  • Topology:
    Transformerless
  • Self consumption (night):
    <2W
  • Operating ambient temperature range:
    - 25~+60℃
  • Relative humidity:
    0~100%
  • Ingress protection:
    IP66
  • Noise emission(typical):
    ≤ 55dB(A)
  • Cooling concept:
    Fan cooling
  • Max.operation altitude:
    4000m

Standards

  • Grid connection standard:
    EN50549, G99, AS4777.2-2015, VDE0126-1-1, IEC62727, VDE4105-2018, IEE1547, UL1741SA
  • Safty/EMC standard:
    IEC62109-1/-2, NB/T32004-2018, EN61000-6-1, EN61000-6-3, UL1741, FCC

Features

  • DC connection:
    MC4
  • AC connection:
    OT Terminal connectors
  • Display:
    LCD, 2×20 Z.
  • Communication:
    RS485 /PLC (optional)
  • Warranty:
    5 Years /10 Years /15 Years /20 Years

Input DC

  • Recommended Max. DC input power (kW):
    126
  • Max. DC input voltage(V):
    1100
  • Nominal DC voltage(V):
    720
  • Start-up voltage(V):
    200
  • MPPT voltage range(V):
    180-1000
  • Full load MPPT voltage range (V):
    505-850
  • Max. input current (A):
    26A
  • Max. Short Circuit current for each MPPT:
    40A
  • MPPT number/Max input strings number:
    9/A:2; B:2; C:2; D:2; E:2; F:2; G:2; H:2; I:2

Output AC

  • Rated output power(kW):
    100kW
  • Max. apparent output power(kVA):
    110kVA
  • Max. output power:
    110kW
  • Rated grid voltage(V):
    3/PE, 480V
  • Rated grid frequency(Hz):
    50Hz/60Hz
  • AC Output frequency range:
    45 ~ 55Hz/55 ~ 60Hz
  • Rated grid current:
    120.3A
  • Max. output current:
    132.3A
  • Power Factor (at rated output power):
    0.8leading ... 0.8lagging
  • THDi (at rated output power):
    <3%
  • DC injection current:
    0.5%In

Efficiency

  • Max.efficiency:
    99.00%
  • EU efficiency:
    98.40%
  • MPPT efficiency:
    99.5%

Protection

  • Anti-islanding protection:
    Yes
  • DC reverse-polarity protection:
    Yes
  • Insulation resistance monitoring:
    Yes
  • Residual current detection:
    Yes
  • DC Surge protection:
    Type Ⅱ /Type Ⅰ + Ⅱ
  • AC Surge protection:
    Type Ⅱ
  • Grid monitoring:
    Yes
  • Strings Monitoring:
    Yes
  • I/V Curve scanning:
    Yes
  • Anti-PID function:
    Yes
  • DC are-fault circuit protection:
    Yes
  • Intergarated DC switch:
    Yes
  • Intergarated AC switch:
    Optional

General Data

  • Dimensins(W*H*D):
    1050W*567H*286.5D
  • Weight(kg):
    <85kg
  • Topology:
    Transformerless
  • Self consumption (night):
    <2W
  • Operating ambient temperature range:
    - 25~+60℃
  • Relative humidity:
    0~100%
  • Ingress protection:
    IP66
  • Noise emission(typical):
    ≤ 55dB(A)
  • Cooling concept:
    Fan cooling
  • Max.operation altitude:
    4000m

Standards

  • Grid connection standard:
    EN50549, G99, AS4777.2-2015, VDE0126-1-1, IEC62727, VDE4105-2018, IEE1547, UL1741SA
  • Safty/EMC standard:
    IEC62109-1/-2, NB/T32004-2018, EN61000-6-1, EN61000-6-3, UL1741, FCC

Features

  • DC connection:
    MC4
  • AC connection:
    OT Terminal connectors
  • Display:
    LCD, 2×20 Z.
  • Communication:
    RS485 /PLC (optional)
  • Warranty:
    5 Years /10 Years /15 Years /20 Years